1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
|
// SPDX-License-Identifier: GPL-2.0-or-later
/*
* pid.c PID controller for testing cooling devices
*
* Copyright (C) 2012 Intel Corporation. All rights reserved.
*
* Author Name Jacob Pan <jacob.jun.pan@linux.intel.com>
*/
#include <unistd.h>
#include <stdio.h>
#include <stdlib.h>
#include <string.h>
#include <stdint.h>
#include <sys/types.h>
#include <dirent.h>
#include <libintl.h>
#include <ctype.h>
#include <assert.h>
#include <time.h>
#include <limits.h>
#include <math.h>
#include <sys/stat.h>
#include <syslog.h>
#include "tmon.h"
/**************************************************************************
* PID (Proportional-Integral-Derivative) controller is commonly used in
* linear control system, consider the the process.
* G(s) = U(s)/E(s)
* kp = proportional gain
* ki = integral gain
* kd = derivative gain
* Ts
* We use type C Alan Bradley equation which takes set point off the
* output dependency in P and D term.
*
* y[k] = y[k-1] - kp*(x[k] - x[k-1]) + Ki*Ts*e[k] - Kd*(x[k]
* - 2*x[k-1]+x[k-2])/Ts
*
*
***********************************************************************/
struct pid_params p_param;
/* cached data from previous loop */
static double xk_1, xk_2; /* input temperature x[k-#] */
/*
* TODO: make PID parameters tuned automatically,
* 1. use CPU burn to produce open loop unit step response
* 2. calculate PID based on Ziegler-Nichols rule
*
* add a flag for tuning PID
*/
int init_thermal_controller(void)
{
/* init pid params */
p_param.ts = ticktime;
/* TODO: get it from TUI tuning tab */
p_param.kp = .36;
p_param.ki = 5.0;
p_param.kd = 0.19;
p_param.t_target = target_temp_user;
return 0;
}
void controller_reset(void)
{
/* TODO: relax control data when not over thermal limit */
syslog(LOG_DEBUG, "TC inactive, relax p-state\n");
p_param.y_k = 0.0;
xk_1 = 0.0;
xk_2 = 0.0;
set_ctrl_state(0);
}
/* To be called at time interval Ts. Type C PID controller.
* y[k] = y[k-1] - kp*(x[k] - x[k-1]) + Ki*Ts*e[k] - Kd*(x[k]
* - 2*x[k-1]+x[k-2])/Ts
* TODO: add low pass filter for D term
*/
#define GUARD_BAND (2)
void controller_handler(const double xk, double *yk)
{
double ek;
double p_term, i_term, d_term;
ek = p_param.t_target - xk; /* error */
if (ek >= 3.0) {
syslog(LOG_DEBUG, "PID: %3.1f Below set point %3.1f, stop\n",
xk, p_param.t_target);
controller_reset();
*yk = 0.0;
return;
}
/* compute intermediate PID terms */
p_term = -p_param.kp * (xk - xk_1);
i_term = p_param.kp * p_param.ki * p_param.ts * ek;
d_term = -p_param.kp * p_param.kd * (xk - 2 * xk_1 + xk_2) / p_param.ts;
/* compute output */
*yk += p_term + i_term + d_term;
/* update sample data */
xk_1 = xk;
xk_2 = xk_1;
/* clamp output adjustment range */
if (*yk < -LIMIT_HIGH)
*yk = -LIMIT_HIGH;
else if (*yk > -LIMIT_LOW)
*yk = -LIMIT_LOW;
p_param.y_k = *yk;
set_ctrl_state(lround(fabs(p_param.y_k)));
}
|